Maximum Photovoltaic Input Power

400KW

Rated Current

606A

Rated Input Voltage

3W+N+PE,380/400V

Rated Frequency

50Hz/60Hz

Voltage Range

DC580V~DC900V

DC Channel

5

Single Channel Rated Current

170A

Rated Power

500kW

Rated Grid Voltage

3W+N+PE, 380V/400V

Grid Voltage Range

-15%~+10%

Rated Grid Frequency

50Hz/60Hz

Grid Frequency Range

±2Hz

Output Current Distortion

≤ 3% (rated power)

DC Component

<0.5%In

Power Factor Range

-0.9~+0.9

AC Specifications

500kW

Maximum Output Power

525kV A

Rated Output Voltage

3W+N+PE, 380/400V

Output Voltage Distortion

3%

Rated Frequency

50Hz/60Hz

Overload Capacity

105%]: continuous operation; (105%-120%]: 10 min; 120%): 1 min

Battery Type

Lithium iron phosphate

Number of Battery Cabinets 5
Battery System Capacity

1075.2kWh

Rated Run Time 2h (Runtime adjustable by modifying the number of battery modules)
Cycle Life

6.000 times (0.5C @ 25°C charge and discharge @ 90% DOD, EOL 80%)

Dimensions (WDH) (mm)

6058*2438*2591

Net weight

16000Kg

Standalone Mode

Integrated Isolation Transformer

Grid-Connected & Off-Grid Switching Device

STS Electronic Switch

Protection Standard IP54 Protection Standard for Outdoor Equipment
Operating Temperature Range

-20°C to 55°C (Performance derates above 45°C)

Relative Humidity (Non-Condensing)

0% RH – 95% RH (non-condensing)

Temperature Control Method

Battery Compartment: Air Conditioning Cooling
Electrical Compartment: Fan Cooling

Maximum Operating Altitude

2.000m at 45°C

Display Screen

Touch Screen

External Communication Interface

RS485、LAN

Communication Protocol

Modbus-RTU、Modbus-TCP